Product Detailed
1.Economical and practical 2.Simple construction and easy operation 3.Up to standard GB3804-2004,GB3906-2006

The load switch is used for electrical equipment protection and control.

Normal use setting:

a) Environmental  temperature

Tmax : +40 centigrade   Tmin: -40 centigrade

Daily average value: ≤ 35 centigrade

Ambient humidity: Daily average relative humidity: ≤ 95%   Monthly average relative humidity: ≤ 90% 

Daily average vapor pressure: ≤ 2.2 × 10-3Mpa   Monthly average vapor pressure: ≤ 1.8 × 10-3Mpa  

b) altitude: ≤  2000m

c) Earthquake intensity:≤ 8degree

d) The use place should be without drip , dewing ,inflammable and explosive danger,chemical corrosive gases and violent vibration.

Product standards:

GB3804-2004,GB3906-2006,GB16926-2009,GB/T11022-2011

Designation        UnitFLN48-12D/T630-20 Load Switch
Rated voltage        KV12   
Rated frequency        Hz50   
Rated current        A630   
1 min power frequency withstand voltage,relative,interphase/fracture  KV42/48   
Lightning impulse withstand voltage (peak)relatively,interphase/fracture KV75/85   
Rated power frequency withstand voltage under 5min zero gauge pressure  KV24   
Rated short-time withstand current for 3 seconds/2 seconds load switch/earthing switchKA20/20   
Rated dynamic current(peak) load switch/earthing switch   KA50/50   
Rated short-circuit making current   load switch/earthing switch  KA50/50   
Rated closed-loop dropout current      A630   
Rated active load dropout current      A630   
Rated cable-charging dropout current     A10   
Rated short-circuit dropout current     KA    
Rated transfer current       A    
Fuse type             
Fuse impact energy output       J    
Mechanical life load switch/earthing switch     times5000/2000  
Charged body and ground air insulating distance    mm≥125   
SF6 gas pressure(relative pressure at 20 centigrade)    bar0.4   
Switching synchronization status      ms≤2   
Main circuit resistance       µΩ≤65   